Overview
The Metrel MI 3136 InstalTest COMBO XC Advanced Installation Testing Kit combines essential electrical installation tests with a modern colour touchscreen and onboard result storage. Suitable for installation verification to AS/NZS 3000 and testing to AS/NZS 3017, it brings insulation resistance, continuity, RCD testing, loop impedance and phase rotation testing together in one portable instrument.
This Advanced Kit adds a padded carrying bag, remote test probe, switchboard resistor box, 4m trailing earth lead and non-contact voltage detector to the standard instrument package. Our TTS package also includes a USB-C charger, 100 switchboard test tags and 200 RCD test tags.
The 4.3-inch touchscreen makes selecting tests, viewing results and organising records easy. Preset and adjustable PASS/FAIL limits help assess measurements, while automatic test sequences reduce repetitive setup when testing multiple circuits or RCDs.
The instrument uses the same operating software as the other Metrel testers of this generation including simple formats for organising site structures. These structures can be configured on the tester at the time of testing or uploaded prior to site visit from a Windows PC.
The MI 3136 features Autotest sequences with built-in preconfigured PASS/FAIL thresholds for Australian installation testing to AS/NZS 3000.
The socket testing function checks earth continuity, polarity and correct circuit connections. With the included A1195 resistor box positioned at the switchboard, it supports socket testing without a lengthy trailing earth lead. An optional A1532 XA EVSE adaptor extends the tester's capabilities to compatible electric vehicle charging stations.
A rechargeable lithium-ion battery, USB-C charging, Bluetooth and Wi-Fi connectivity support everyday testing and data management. Metrel ES Manager BASIC software is included, with additional reporting and cloud functions available through optional licences.
Note: This product is an installation tester. It is not a portable appliance tester and is not intended for routine appliance test and tag work.
Applications
The MI 3136 supports the following installation verification and electrical testing applications:
- Voltage and frequency
- Phase rotation
- Resistance of earth connections and equipotential bonding
- Low-current continuity
- Insulation resistance
- Socket polarity and correct circuit connections
- Fault loop impedance and prospective fault current
- Line impedance and prospective short-circuit current
- RCD trip time, ramp current and automatic testing
- Contact voltage
- Voltage drop
- Three-wire earth resistance testing with optional accessories
Specifications
Insulation Resistance
Selectable test voltages of 50V, 100V, 250V, 500V and 1000V DC, with automatic discharge after testing.
Nominal Voltages: 50V, 100V & 250V DC
| Measuring Range (MΩ) | Resolution (MΩ) | Accuracy |
|---|---|---|
| 0.00 ... 19.99 | 0.01 | ±(5% of reading + 3 digits) |
| 20.0 ... 99.9 | 0.1 | ±(10% of reading) |
| 100.0 ... 199.9 | 0.1 | ±(20% of reading) |
Nominal Voltage: 500V DC
| Measuring Range (MΩ) | Resolution (MΩ) | Accuracy |
|---|---|---|
| 0.00 ... 19.99 | 0.01 | ±(5% of reading + 3 digits) |
| 20.0 ... 199.9 | 0.1 | ±(5% of reading) |
| 200 ... 999 | 1 | ±(10% of reading) |
Nominal Voltage: 1000V DC
| Measuring Range (MΩ) | Resolution (MΩ) | Accuracy |
|---|---|---|
| 0.00 ... 19.99 | 0.01 | ±(5% of reading + 3 digits) |
| 20.0 ... 199.9 | 0.1 | ±(5% of reading) |
| 200 ... 999 | 1 | Indicative only |
Voltage During Insulation Testing
Displays the applied insulation test voltage. This is separate from the general voltage measurement function.
| Measuring Range (V) | Resolution (V) | Accuracy |
|---|---|---|
| 0 ... 1200 | 1 | ±(3% of reading + 3 digits) |
Resistance (R LOWΩ)
Measures protective conductor and equipotential bonding resistance using a minimum 200mA test current into a 2Ω load. Automatic polarity reversal and test lead compensation support reliable low-resistance measurements.
Measuring Range
| Measuring Range (Ω) | Resolution (Ω) | Accuracy |
|---|---|---|
| 0.00 ... 19.99 | 0.01 | ±(3% of reading + 3 digits) |
| 20.0 ... 199.9 | 0.1 | ±(5% of reading) |
| 200 ... 1999 | 1 | ±(5% of reading) |
RCD Testing
General Data
- Supported RCD types include AC, A, F, B and B+
- Nominal residual current settings from 6mA to 1000mA, depending on the selected protective device
- Sine-wave, pulsed and DC test currents
- Test current starting polarity: 0°, 180° or both
- Trip time, trip current and contact voltage measurements
- Automatic RCD test sequences
- Selectable AS/NZS 3017 test settings
Available test currents, multipliers and test durations depend on the selected RCD type and test configuration.
Trip-out Time
| Measuring Range (ms) | Resolution (ms) | Accuracy |
|---|---|---|
| 0.0 ... 40.0 | 0.1 | ±1ms |
| 40.1 ... 999.9 | 0.1 | ±3ms |
| 1000 ... 1999 | 1 | ±3ms |
| 2000 ... 10000 | 10 | ±10ms |
Trip-out Current
| Measuring Range | Resolution | Accuracy |
|---|---|---|
| 0.1 ... 99.9mA | 0.1mA | ±10% |
| 100 ... 999mA | 1mA | ±10% |
| 1.00 ... 1.10A | 10mA | ±10% |
Socket Test
The Australian socket test function combines earth continuity, polarity and correct connection checks into a single push-button sequence, with clear PASS/FAIL results.
The included A1195 resistor box connects at the switchboard to support testing at socket outlets without a trailing earth lead. This accessory is part of the Advanced Kit supplied here.
Fault Loop Impedance
Without RCD Protection
| Measuring Range (Ω) | Resolution (Ω) | Accuracy |
|---|---|---|
| 0.00 ... 9.99 | 0.01 | ±(3% of reading + 3 digits) |
| 10.0 ... 99.9 | 0.1 | ±(3% of reading + 3 digits) |
| 100 ... 999 | 1 | ±(10% of reading) |
| 1000 ... 9990 | 10 | ±(10% of reading) |
With RCD Protection – Standard Test Current Mode
| Measuring Range (Ω) | Resolution (Ω) | Accuracy |
|---|---|---|
| 0.00 ... 9.99 | 0.01 | ±(5% of reading + 10 digits) |
| 10.0 ... 99.9 | 0.1 | ±(5% of reading + 10 digits) |
| 100 ... 999 | 1 | ±(10% of reading) |
| 1000 ... 9990 | 10 | ±(10% of reading) |
Prospective Fault Current (Calculated Value)
| Measuring Range (A) | Resolution (A) | Accuracy |
|---|---|---|
| 0.00 ... 9.99 | 0.01 | Dependent on loop impedance measurement |
| 10.0 ... 99.9 | 0.1 | Dependent on loop impedance measurement |
| 100 ... 999 | 1 | Dependent on loop impedance measurement |
| 1000 ... 9990 | 10 | Dependent on loop impedance measurement |
| 10000 ... 23000 | 100 | Dependent on loop impedance measurement |
Voltage, Frequency & Phase Rotation
Voltage
- Result type: True RMS
- Real-time monitoring of voltages between the connected test terminals
| Measuring Range (V) | Resolution (V) | Accuracy |
|---|---|---|
| 0 ... 550 | 1 | ±(2% of reading + 2 digits) |
Frequency
| Measuring Range (Hz) | Resolution (Hz) | Accuracy |
|---|---|---|
| 14.0 ... 499.9 | 0.1 | ±(0.2% of reading + 1 digit) |
Phase Rotation
- Nominal system voltage: 100V ... 550V AC
- Nominal frequency: 14Hz ... 500Hz
- Displays phase sequence as 1.2.3 or 3.2.1
General Data
- Overvoltage Category: 600V CAT III / 300V CAT IV
- Protection Degree: IP40
- Protection Class: Double insulation
- Display: 4.3-inch colour TFT capacitive touchscreen, 480 x 272 pixels
- Power Supply: 7.2V, 5200mAh rechargeable lithium-ion battery pack
- Charging: USB Type-C Power Delivery
- Typical Battery Operation: 14 hours
- Connectivity: USB-C, Bluetooth and Wi-Fi
- Result Storage: microSD-based memory
- Operating Temperature: 0°C to 40°C
- Maximum Operating Humidity: 90% RH, non-condensing
Measurement categories vary with the connected leads and accessories. Refer to the instrument manual for full specifications and operating conditions.
Result Storage & Reporting
Store measurements against organised installation records using the onboard Memory Organizer. Saved results can be transferred to Metrel ES Manager for further processing and record keeping.
The standard set includes a Metrel ES Manager BASIC licence. Advanced reporting and cloud workflows require the applicable MESM PRO and Metrel Cloud licences.
Contents
This package comprises the MI 3136 standard instrument set, the Advanced Kit accessories and the additional consumables and charger supplied by TTS.
MI 3136 Instrument and Standard Accessories
- Metrel MI 3136 InstalTest COMBO XC instrument
- Rechargeable lithium-ion battery pack
- 3 x Test probes: brown, blue and green
- 3 x Crocodile clips: brown, blue and green
- Three-wire test cable, 1.5m
- Mains measuring cable, 1.5m
- USB Type-C cable
- Calibration certificate
- Short instruction manual
- Instruction manual, available to download
- Metrel ES Manager software with BASIC licence
Advanced Kit Accessories
- A1551 large padded carrying bag
- A1401 remote test probe for XC/XD series
- A1195 resistor box for socket testing
- A1012 green trailing earth lead, 4m
- MD-106 non-contact voltage detector
Additional Items Included by TTS
- USB-C charger
- 100 x switchboard test tags
- 200 x RCD test tags
Optional accessories: Earth resistance test set and A1532 XA EVSE adaptor are available separately.
Warranty
Manufacturer's warranty applies. Please contact us for warranty details.
Collapsible content
Printer Label Guide
BUYING GUIDE
Need help with find the right option?
Our buying guide takes the guess work out of finding the perfect tester for your needs